이동식 생물안전 연구시설 내 공조공기 급·배기구의 위치선정에 관한 해석적 연구
(주)코리아스칼라
- 최초 등록일
- 2023.11.20
- 최종 저작일
- 2023.10
- 6페이지/ 어도비 PDF
- 가격 4,000원
* 본 문서는 배포용으로 복사 및 편집이 불가합니다.
서지정보
ㆍ발행기관 : 한국기계기술학회
ㆍ수록지정보 : 한국기계기술학회지 / 25권 / 5호
ㆍ저자명 : 김영득, 이주성
영어 초록
Recently a biosafety level-3(BL-3) mobile laboratory has been set up for the virus scanning and vaccine development because of the COVID-19 pandemic. The study on air flow inlet and outlet location and its flow direction with ventilation in the mobile laboratory needs to prevent spread of COVID-19 virus because the COVID-19 virus is primarily transmitted to people through respiratory droplets and aerosol coming out as their coughing. This study is conducted on the air flow pattern optimization in BL-3 mobile laboratory with various design specifications of position of air supply & exhaust port and particle source. Air flow patterns of ceiling supply-exhaust and ceiling supply-bottom side exhaust with particle source were determined to compare the impact of the infection prevention. CFD simulation was used to analyze for two air flow patterns and particle source position. Numerical results showed that air flow pattern of air conditioning system with ceiling supply-exhaust in a row is more effective than that of ceiling supply-bottom side exhaust air flow pattern in terms of infection prevention in biosafety mobile laboratory.
참고 자료
없음
"한국기계기술학회지"의 다른 논문
더보기 (5/10)