서고환경의 실내공기질에 관한 연구
(주)코리아스칼라
- 최초 등록일
- 2016.04.01
- 최종 저작일
- 2009.06
- 10페이지/ 어도비 PDF
- 가격 4,000원
* 본 문서는 배포용으로 복사 및 편집이 불가합니다.
서지정보
ㆍ발행기관 : 한국실내환경학회
ㆍ수록지정보 : 한국실내환경학회지 / 6권 / 2호
ㆍ저자명 : 이철민, 김우재, 이정주, 봉춘근, 조장우, 김윤신
영어 초록
The purpose of this study are to examin the level of temperature, relative humidity and pollutants at stock rooms in National Archives and to provide fundamental data in order to protect damage of archives. The survey of indoor air quality(IAQ) in stock rooms was performed in Busan National Archives in August and December 2007, and collected basic data, on level of them at stock rooms in National Archives that were published. The temperature and relative humidity in stock rooms were within the terms of national law of the public archives administration. The concentration of PM10 in stock rooms in National Archives exceeded 50 ㎍/m<sup>3</sup>, which is the guideline of national law for the public archives administration. The concentration of CO, SO<sub>2</sub>, NO<sub>2</sub>, O<sub>3</sub> and Formaldehyde in stock rooms did not exceeded the guideline of national law. The concentration of total volatile organic compounds was shown to exceed the guideline of natioanl law. Therefore, we suggest that a national plan for the management of IAQ at stock rooms in National Archives should be established through a long-term, continuous investigation