학교교실의 냉방시 실내열 • 공기환경 실태
(주)학지사
- 최초 등록일
- 2015.03.25
- 최종 저작일
- 2007.07
- 10페이지/ 어도비 PDF
- 가격 3,000원
* 본 문서는 배포용으로 복사 및 편집이 불가합니다.
서지정보
ㆍ발행기관 : 한국주거학회
ㆍ수록지정보 : 한국주거학회논문집 / 18권 / 4호
ㆍ저자명 : 최윤정, 정연홍, 이선아, 김혜경, 황진아
목차
Abstract
Ⅰ. 서론
Ⅱ. 문헌고찰
Ⅲ. 연구방법
Ⅳ. 측정결과 및 해석
Ⅴ. 결론 및 제언
참고문헌
영어 초록
The purpose of this study were to make clear the present condition of indoor thermal and air environment by cooling in school classrooms and to analyze the relation of the living conditions with indoor environment. The measurements on physical elements and observations on living conditions were carried out in 6 classrooms of 3 middle or high schools. Measuring elements were indoor temperature, relative humidity, PM10 and CO₂ concentration. As results, the averages of indoor temperature each classrooms were 24.9~26.6°C. Most of classrooms were lower than the Maintenance standard (26~28°C) of School Health Law. The means of relative humidity were 51.3~72%, all classrooms were ranged within the standard (30~80%). The means of PMlO concentration were 3.5~23.1 µg/㎥, all classrooms were kept within the standard (100 µg/㎥). The means of CO₂ concentration were 1218.7~4705.4 ppm, all classrooms were exceed the standard (1,000 ppm). The results of analysis on relations of living conditions with the physical elements are as follow; the air conditioner set of temperature, windows and doors opening elapsed time, the number of students in classrooms and activities of students had certain effect on indoor environment.