지하상업공간의 환기계수 및 화재하중 분석
(주)학지사
- 최초 등록일
- 2015.03.24
- 최종 저작일
- 2006.01
- 8페이지/ 어도비 PDF
- 가격 3,000원
* 본 문서는 배포용으로 복사 및 편집이 불가합니다.
서지정보
ㆍ발행기관 : 한국주거학회
ㆍ수록지정보 : 한국주거학회논문집 / 17권 / 2호
ㆍ저자명 : 추연희, 이지희, 홍원화
목차
I. 서 론
II. 이론적 고찰
III. 환기계수 및 화재하중 현장조사 결과
IV. 결 론
한국어 초록
The purpose of this study is to obtain the fire safety for underground commercial space with analysing fire loads and ventilation factors. It was adopted the investigation method of field survey with commercial uses for more confidential data. The results of this study can be summarized as follows; 1) The ventilation factor shows 0.04~0.24 m1/2 and it may develop ventilation-controlled fires which have much fire hazard more than fuel-controlled fires.2) The highest value of fire load is 158.48 kg/m2 and appeared in footwear shop which has the value 137.35 kg/m2 for unfixed combustibles and 21.13 kg/m2 for fixed combustibles.3) The average value of burning rates which mean the velocity of fire development and the fire damage range is 0.143. Therefore it is desired to decrease the combustibles of compartment and is needed the method of dispersion arrangement of goods and storage to steel cabinet and so on.Keywords : Underground Commercial Space, Fire Load, Ventilation Factor, Burning rate주 요 어 : 지하상업공간, 화재하중, 환기계수, 연소속도
참고 자료
없음
"한국주거학회논문집"의 다른 논문
더보기 (5/10)